Deltaww DVP-12SE
DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability
Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions.
Affected versions and mitigation
From the CVE record and the vendor's references.Mitigation
The record names no fix. Check the vendor advisory below.
Workaround
Users are recommended to take the following mitigation measures: * Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access. * Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with. * Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.
Timeline
Days relative to CVE publicationNo public PoC found yet; not in CISA KEV.
PoC repositories
Found on GitHub.No PoC repositories found yet.