  "id": "CVE-2026-12819",
  "url": "https://poc.griffinguard.io/cve/CVE-2026-12819",
  "published_at": "2026-06-30T06:28:51.514Z",
  "title": "DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability",
  "vendor": "deltaww",
  "product": "DVP-12SE",
  "cvss": {
    "score": 9.3,
    "source": "cna",
    "vector": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions.",
  "cwe": "CWE-306",
  "cvss_by_source": {
    "cna": 9.3
  },
  "repos": [],
  "remediation": {
    "workarounds": [
      "Users are recommended to take the following mitigation measures:\n\n  *  Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.\n\n  *  Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.\n\n  *  Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel."
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}