Grid Protection Alliance openPDC and openHistorian Missing Authentication for Critical Function
The internal data publisher on openPDC accepts network connections without authentication in its default configuration. An unauthenticated network attacker can connect to this interface and retrieve the complete device and measurement topology of the system.
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
- < 2.9.477
- < 2.9.482
Fixed in 2.9.477, 2.9.482
- < 2.9.477
- < 2.9.482
Fixed in 2.9.477, 2.9.482
- < 2.8.580
- < 2.8.585
Fixed in 2.8.580, 2.8.585
Mitigation
Grid Protection Alliance updated the default configuration to bind this interface to the local loopback address only. This change applies to new installations; existing installations upgraded from an earlier version retain their prior configuration and will not receive the new default automatically. Operators should verify their configuration explicitly and update the interface binding if it is still set to accept connections on all interfaces.
Workaround
Grid Protection Alliance does not recommend production use of published Docker images in any case. The fix for this vulnerability has not been published to the Docker image.