Rockwell Automation FLEX 5000 I/O
Rockwell Automation FLEX 5000 I/O - Module Fault
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
First public PoC
None yetno public PoC found
Public PoCs00 on GitHub
CVSS8.7high · scored by CNA · CWE-1287
CISA KEV
Not listednot known exploited
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
Rockwell Automation FLEX 5000 I/O
- Version 2.011 or below
Mitigation
Upgrade to version 2.012 or later
Timeline
Days relative to CVE publicationNo public PoC found yet; not in CISA KEV.
PoC repositories
Found on GitHub.No PoC repositories found yet.