  "id": "CVE-2025-9042",
  "url": "https://poc.griffinguard.io/cve/CVE-2025-9042",
  "published_at": "2025-08-14T14:23:58.491Z",
  "title": "Rockwell Automation FLEX 5000 I/O - Module Fault",
  "vendor": "Rockwell Automation",
  "product": "FLEX 5000 I/O",
  "cvss": {
    "score": 8.7,
    "source": "cna",
    "vector": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.",
  "cwe": "CWE-1287",
  "cvss_by_source": {
    "cna": 8.7
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "Rockwell Automation",
        "product": "FLEX 5000 I/O",
        "ranges": [
          "Version 2.011 or below"
        ],
        "fixed_in": null
      }
    ],
    "solutions": [
      "Upgrade to version 2.012 or later"
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}