Siemens OZW672
Edge device · Device firmwarehardware or firmware CPE: siemens ozw672_firmware (medium confidence)
A vulnerability has been identified in OZW672 (All versions < V8.0), OZW772 (All versions < V8.0). The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.
First public PoC
None yetno public PoC found
Public PoCs00 on GitHub
CVSS10.0critical · scored by CNA · CWE-78
CISA KEV
Not listednot known exploited
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
Siemens OZW672
- < V8.0
Fixed in V8.0
Siemens OZW772
- < V8.0
Fixed in V8.0
Mitigation
Upgrade OZW672 to V8.0 or later.
Upgrade OZW772 to V8.0 or later.
Timeline
Days relative to CVE publicationNo public PoC found yet; not in CISA KEV.
PoC repositories