  "id": "CVE-2025-26389",
  "url": "https://poc.griffinguard.io/cve/CVE-2025-26389",
  "published_at": "2025-05-13T09:38:34.471Z",
  "vendor": "Siemens",
  "product": "OZW672",
  "cvss": {
    "score": 10,
    "source": "cna",
    "vector": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": {
    "category": "Device firmware",
    "confidence": "medium",
    "reason": "hardware or firmware CPE: siemens ozw672_firmware"
  },
  "description": "A vulnerability has been identified in OZW672 (All versions \u003c V8.0), OZW772 (All versions \u003c V8.0). The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.",
  "cwe": "CWE-78",
  "cpes": [
    "cpe:2.3:o:siemens:ozw672_firmware:*:*:*:*:*:*:*:*",
    "cpe:2.3:o:siemens:ozw772_firmware:*:*:*:*:*:*:*:*"
  ],
  "cvss_by_source": {
    "cna": 10,
    "nvd": 9.8
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "Siemens",
        "product": "OZW672",
        "ranges": [
          "\u003c V8.0"
        ],
        "fixed_in": [
          "V8.0"
        ]
      },
      {
        "vendor": "Siemens",
        "product": "OZW772",
        "ranges": [
          "\u003c V8.0"
        ],
        "fixed_in": [
          "V8.0"
        ]
      }
    ],
    "upgrade": [
      "Upgrade OZW672 to V8.0 or later.",
      "Upgrade OZW772 to V8.0 or later."
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}