CVE-2026-61884published 24 Jul 2026 21:40 UTCData: JSON · API

Tycon Systems TPDIN-Monitor-WEB2

Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function

The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.

First public PoC None yetno public PoC found
Public PoCs00 on GitHub
CVSS9.8critical · scored by CNA · CWE-306
CISA KEV Not listednot known exploited

Affected versions and mitigation

From the CVE record and the vendor's references.

Affected

Tycon Systems TPDIN-Monitor-WEB2
  • < 2.4.5

Fixed in 2.4.5

Mitigation

Tycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to security@tyconsystems.com. Tycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset. Tycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN.

Timeline

Days relative to CVE publication
-2t=0+2+4+6+8CVE published24 Jul 2026 · t = 0

No public PoC found yet; not in CISA KEV.

PoC repositories

Found on GitHub.

No PoC repositories found yet.