RT-Labs P-Net
Resource exhaustion from unreleased AR and RPC session on RPC requests with incorrect endianness
P-Net before 1.0.3 does not release the Application Relationship (AR) and the RPC session when an RPC request is rejected because its data representation has incorrect endianness. The session and its AR remain allocated, so repeated requests exhaust the available sessions. Once they are exhausted the device no longer answers new RPC requests, including Connect, until it is restarted. A remote unauthenticated attacker can use this to cause a denial of service.
First public PoC
None yetno public PoC found
Public PoCs00 on GitHub
CVSS8.7high · scored by CNA · CWE-772
CISA KEV
Not listednot known exploited
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
RT-Labs P-Net
- < 1.0.3
Fixed in 1.0.3
Mitigation
Upgrade to P-Net 1.0.3 or later.
Timeline