Rockwell Automation PLC - Micro850 L50E
Rockwell Automation Micro800 Vulnerability
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
First public PoC
None yetno public PoC found
Public PoCs00 on GitHub
CVSS9.3critical · scored by CNA · CWE-20
CISA KEV
Not listednot known exploited
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
Rockwell Automation PLC - Micro850 L50E
- V20.011 - V22.011
Mitigation
V23.011 and later
Timeline
Days relative to CVE publicationNo public PoC found yet; not in CISA KEV.
PoC repositories
Found on GitHub.No PoC repositories found yet.