PoC Monitor
← All CVEs
CVE-2025-58473published 23 Sep 2025 22:21 UTCData: JSON · API

AutomationDirect CLICK PLUS C0-0x CPU firmware

AutomationDirect CLICK PLUS Improper Resource Shutdown or Release

An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all available device sessions of the Click Programming Software.

First public PoC None yetno public PoC found
Public PoCs00 on GitHub
CVSS8.2high · scored by CNA · CWE-404
CISA KEV Not listednot known exploited

Affected versions and mitigation

From the CVE record and the vendor's references.

Affected

AutomationDirect CLICK PLUS C0-0x CPU firmware
  • < v3.71

Fixed in v3.71

AutomationDirect CLICK PLUS C0-1x CPU firmware
  • < v3.71

Fixed in v3.71

AutomationDirect CLICK PLUS C2-x CPU firmware
  • < v3.71

Fixed in v3.71

Mitigation

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.

Timeline

Days relative to CVE publication
-2t=0+2+4+6+8CVE published23 Sep 2025 · t = 0

No public PoC found yet; not in CISA KEV.

PoC repositories

Found on GitHub.

No PoC repositories found yet.