Crestron Automate VX
Non-Secure Access
Cleartext Transmission of Sensitive Information vulnerability in Crestron Automate VX allows Sniffing Network Traffic. The device allows Web UI and API access over non-secure network ports which exposes sensitive information such as user passwords. This issue affects Automate VX: from 5.6.8161.21536 through 6.4.0.49.
First public PoC
None yetno public PoC found
Public PoCs00 on GitHub
CVSS10.0critical · scored by CNA · CWE-319
CISA KEV
Not listednot known exploited
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
Crestron Automate VX
- >= 5.6.8161.21536, <= 6.4.0.49
Fixed in 6.4.1.8
Mitigation
Crestron recommends updating to firmware version 6.4.1.8 or higher. The firmware version will disables the use of unsecure ports for the Web UI and API.
Workaround
Protect the device at the physical or network layer using an external firewall to prevent unauthorized configuration.
References
- Vendor advisory security.crestron.com
- Patch crestron.com/Software-Firmware/Software/Automate…
- Release notes crestron.com/release_notes/automate_vx_6.4.1.8_r…
Timeline
Days relative to CVE publicationNo public PoC found yet; not in CISA KEV.
PoC repositories
Found on GitHub.No PoC repositories found yet.