Optigo Networks ONS NC600
Use of Hard-coded Credentials Optigo Networks ONS NC600
In Optigo Networks ONS NC600 versions 4.2.1-084 through 4.7.2-330, an attacker could connect with the device's ssh server and utilize the system's components to perform OS command executions.
First public PoC
None yetno public PoC found
Public PoCs00 on GitHub
CVSS9.3critical · scored by CNA · CWE-798
CISA KEV
Not listednot known exploited
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
Optigo Networks ONS NC600
- >= 4.2.1-084, <= 4.7.2-330
Mitigation
Optigo Networks recommends users implement at least one of the following additional mitigations: * Use a dedicated NIC on the BMS computer and exclusively use the computer for connecting to OneView to manage your OT network configuration. * Set up a router firewall with a white list for the devices permitted to access OneView. * Connect to OneView via secure VPN.