Rockwell Automation Micro820®, Micro850®, Micro870®
Micro820®, Micro850®, Micro870® – Specialized Fuzzing Vulnerabilities
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
Affected versions and mitigation
From the CVE record and the vendor's references.Affected
- V23.011 and below
- V12.013 and lower
- V14.011 and lower
Mitigation
V23.012 https://compatibility.rockwellautomation.com/Pages/MultiProductFindDownloads.aspx , Migrate to the newer Micro850/870 controllers (L50E/L70E V23.012 https://compatibility.rockwellautomation.com/Pages/MultiProductFindDownloads.aspx ) , Migrate to the newer Micro820 controllers (L20E V23.011)
Timeline
Days relative to CVE publicationNo public PoC found yet; not in CISA KEV.
PoC repositories
Found on GitHub.No PoC repositories found yet.