  "id": "CVE-2026-66360",
  "url": "https://poc.griffinguard.io/cve/CVE-2026-66360",
  "published_at": "2026-07-30T22:25:54.454Z",
  "title": "MZ Automation libiec61850 Out-of-bounds Read",
  "vendor": "MZ Automation GmbH",
  "product": "libiec61850",
  "cvss": {
    "score": 8.7,
    "source": "cna",
    "vector": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "The ISO Presentation layer contains a flaw in the handling of specific \nparameters during normal mode negotiation. A missing length check in the\n processing of the encoded presentation data allows an attacker \ncontrolled field with a zero length value to trigger a bounded heap over\n read. This condition occurs before MMS session establishment, a crafted\n TCP/102 connection attempt can trigger the issue. The resulting over \nread causes the process to terminate, leading to a denial of service \ncondition.",
  "cwe": "CWE-125",
  "cvss_by_source": {
    "cna": 8.7
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "MZ Automation GmbH",
        "product": "libiec61850",
        "ranges": [
          "\u003c 1.6.2"
        ],
        "fixed_in": [
          "1.6.2"
        ]
      }
    ],
    "solutions": [
      "MZ Automation GmbH recommends that users update to version 1.6.2."
    ],
    "upgrade": [
      "Upgrade libiec61850 to 1.6.2 or later."
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}