  "id": "CVE-2026-119746",
  "url": "https://poc.griffinguard.io/cve/CVE-2026-119746",
  "published_at": "2026-11-04T15:39:12.767Z",
  "title": "ProSoft ICX35 Login Lockout Bypass via Client-Side Cookies",
  "vendor": "ProSoft Technology",
  "product": "X35-HWC-A",
  "cvss": {
    "score": 8.2,
    "source": "cna",
    "vector": "CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "ProSoft Technology ICX35 devices (X35-HWC-A and ICX35-HWC-E) contain a login lockout bypass in the integrated module web page. The account lockout mechanism that restricts repeated failed authentication attempts is enforced in client-side JavaScript, so a remote attacker can reset the lockout and continue submitting password guesses by deleting the relevant browser cookies, defeating the brute-force protection. This vulnerability has been addressed in version 1.14.158.",
  "cwe": "CWE-307",
  "cvss_by_source": {
    "cna": 8.2
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "ProSoft Technology",
        "product": "X35-HWC-A",
        "ranges": [
          "\u003c= 1.14.153"
        ],
        "fixed_in": [
          "1.14.158"
        ]
      },
      {
        "vendor": "ProSoft Technology",
        "product": "ICX35-HWC-E",
        "ranges": [
          "\u003c= 1.14.153"
        ],
        "fixed_in": [
          "1.14.158"
        ]
      }
    ],
    "upgrade": [
      "Upgrade X35-HWC-A to 1.14.158 or later.",
      "Upgrade ICX35-HWC-E to 1.14.158 or later."
    ],
    "references": [
      {
        "kind": "Vendor advisory",
        "url": "https://assets.belden.com/asset/3be80067-b211-423d-9be4-4e31bd43fbc9/PSIRT-9-Login-Lockout-Resets-in-ICX35.pdf"
      }
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}