  "id": "CVE-2026-118498",
  "url": "https://poc.griffinguard.io/cve/CVE-2026-118498",
  "published_at": "2026-11-17T09:10:47.524Z",
  "title": "Improper Limitation of a Pathname to a Restricted Directory in CODESYS Automation Server Connector",
  "vendor": "CODESYS",
  "product": "Automation Server Connector",
  "cvss": {
    "score": 7.5,
    "source": "cna",
    "vector": "CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "The CODESYS Automation Server Connector uses server-supplied file names without sufficient path traversal checks. An unauthenticated remote attacker controlling a malicious Automation Server and tricking a user to trust it, or performing a man-in-the-middle attack on a trusted communication channel, can exploit this vulnerability to write attacker-controlled files to arbitrary locations on the engineering workstation and subsequently achieve arbitrary code execution with user privileges.",
  "cwe": "CWE-22",
  "cvss_by_source": {
    "cna": 7.5
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "CODESYS",
        "product": "Automation Server Connector",
        "ranges": [
          "\u003e= 1.23.0.0, \u003c 1.40.0.0"
        ],
        "fixed_in": [
          "1.40.0.0"
        ]
      }
    ],
    "upgrade": [
      "Upgrade Automation Server Connector to 1.40.0.0 or later."
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}