{
  "id": "CVE-2025-7705",
  "url": "https://poc.griffinguard.io/cve/CVE-2025-7705",
  "published_at": "2025-07-22T11:49:00.964Z",
  "title": "Authentication bypass due to compatibility mode enabled by default",
  "vendor": "ABB",
  "product": "Switch Actuator 4 DU-83330",
  "cvss": {
    "score": 8.6,
    "source": "cna",
    "vector": "CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": ": Active Debug Code vulnerability in ABB Switch Actuator 4 DU-83330, ABB Switch actuator, door/light 4 DU -83330-500.This issue affects Switch Actuator 4 DU-83330: All Versions; Switch actuator, door/light 4 DU -83330-500: All Versions.",
  "cwe": "CWE-489",
  "cvss_by_source": {
    "cna": 8.6
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "ABB",
        "product": "Switch Actuator 4 DU-83330",
        "ranges": [
          "All Versions"
        ],
        "fixed_in": null
      },
      {
        "vendor": "ABB",
        "product": "Switch actuator, door/light 4 DU -83330-500",
        "ranges": [
          "All Versions"
        ],
        "fixed_in": null
      }
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}
