  "id": "CVE-2025-62498",
  "url": "https://poc.griffinguard.io/cve/CVE-2025-62498",
  "published_at": "2025-10-23T21:46:45.36Z",
  "title": "AutomationDirect Productivity Suite Relative Path Traversal",
  "vendor": "AutomationDirect",
  "product": "Productivity Suite",
  "cvss": {
    "score": 8.8,
    "source": "cna",
    "vector": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "A relative path traversal (ZipSlip) vulnerability was discovered in Productivity Suite software version \n\n4.4.1.19. The vulnerability allows an attacker who can tamper with a productivity project to execute arbitrary code on the machine where the project is opened.",
  "cwe": "CWE-23",
  "cvss_by_source": {
    "cna": 8.8
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "AutomationDirect",
        "product": "Productivity Suite",
        "ranges": [
          "\u003c= SW V4.2.1.9"
        ],
        "fixed_in": null
      },
      {
        "vendor": "AutomationDirect",
        "product": "Productivity 3000 P3-622 CPU",
        "ranges": [
          "\u003c= SW V4.2.1.9"
        ],
        "fixed_in": null
      },
      {
        "vendor": "AutomationDirect",
        "product": "Productivity 3000 P3-550E CPU",
        "ranges": [
          "\u003c= SW V4.2.1.9"
        ],
        "fixed_in": null
      },
      {
        "vendor": "AutomationDirect",
        "product": "Productivity 3000 P3-530 CPU",
        "ranges": [
          "\u003c= SW v4.4.1.19"
        ],
        "fixed_in": null
      },
      {
        "vendor": "AutomationDirect",
        "product": "Productivity 2000 P2-622 CPU",
        "ranges": [
          "\u003c= SW v4.4.1.19"
        ],
        "fixed_in": null
      },
      {
        "vendor": "AutomationDirect",
        "product": "Productivity 2000 P2-550 CPU",
        "ranges": [
          "\u003c= SW v4.4.1.19"
        ],
        "fixed_in": null
      },
      {
        "vendor": "AutomationDirect",
        "product": "Productivity 1000 P1-550 CPU",
        "ranges": [
          "\u003c= SW v4.4.1.19"
        ],
        "fixed_in": null
      },
      {
        "vendor": "AutomationDirect",
        "product": "Productivity 1000 P1-540 CPU",
        "ranges": [
          "\u003c SW v4.4.1.19"
        ],
        "fixed_in": [
          "SW v4.4.1.19"
        ]
      }
    ],
    "solutions": [
      "AutomationDirect recommends that users do the following:\n\n  *  Update the Productivity Suite programming software to version 4.5.0.x or higher.\n  *  Update the firmware of Productivity PLCs to the latest version.  https://www.automationdirect.com/support/software-downloads \n  *  Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems.\n  *  It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems.\n  *  AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application."
    ],
    "upgrade": [
      "Upgrade Productivity 1000 P1-540 CPU to SW v4.4.1.19 or later."
    ],
    "workarounds": [
      "AutomationDirect has identified the following mitigations for instances where systems cannot be upgraded to the latest version:\n\n  *  Physically disconnect the PLC from any external networks, including the internet, local area networks (LANs), and other interconnected systems.\n  *  Configure network segmentation to isolate the PLC from other devices and systems within the organization.\n  *  Implement firewall rules or network access control (NAC) policies to block incoming and outgoing traffic to the PLC.\n  *  Please refer to  AutomationDirect's security considerations https://support.automationdirect.com/docs/securityconsiderations.pdf  for additional information.\n  *  If you have any questions regarding this issue, please contact AutomationDirect Technical Support at 770-844-4200 or 800-633-0405 for further assistance."
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}