  "id": "CVE-2025-59484",
  "url": "https://poc.griffinguard.io/cve/CVE-2025-59484",
  "published_at": "2025-09-23T22:08:40.744Z",
  "title": "AutomationDirect CLICK PLUS Use of a Broken or Risky Cryptographic Algorithm",
  "vendor": "AutomationDirect",
  "product": "CLICK PLUS C0-0x CPU firmware",
  "cvss": {
    "score": 8.7,
    "source": "cna",
    "vector": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "The use of a broken or risky cryptographic algorithm was discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software uses an insecure implementation of the RSA encryption algorithm.",
  "cwe": "CWE-327",
  "cvss_by_source": {
    "cna": 8.7
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "AutomationDirect",
        "product": "CLICK PLUS C0-0x CPU firmware",
        "ranges": [
          "\u003c v3.71"
        ],
        "fixed_in": [
          "v3.71"
        ]
      },
      {
        "vendor": "AutomationDirect",
        "product": "CLICK PLUS C0-1x CPU firmware",
        "ranges": [
          "\u003c v3.71"
        ],
        "fixed_in": [
          "v3.71"
        ]
      },
      {
        "vendor": "AutomationDirect",
        "product": "CLICK PLUS C2-x CPU firmware",
        "ranges": [
          "\u003c v3.71"
        ],
        "fixed_in": [
          "v3.71"
        ]
      }
    ],
    "solutions": [
      "AutomationDirect recommends that users update CLICK PLUS and firmware to  V3.80. https://www.automationdirect.com/support/software-downloads \n\nIf the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed:\n\n  *  Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure.\n  *  Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication.\n  *  Access Control – Restrict both physical and logical access to authorized personnel only.\n  *  Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.\n  *  Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.\n  *  Logging \u0026 Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity.\n  *  Backup \u0026 Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.\n  *  Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly."
    ],
    "upgrade": [
      "Upgrade CLICK PLUS C0-0x CPU firmware to v3.71 or later.",
      "Upgrade CLICK PLUS C0-1x CPU firmware to v3.71 or later.",
      "Upgrade CLICK PLUS C2-x CPU firmware to v3.71 or later."
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}