  "id": "CVE-2025-57882",
  "url": "https://poc.griffinguard.io/cve/CVE-2025-57882",
  "published_at": "2025-09-23T22:27:02.078Z",
  "title": "AutomationDirect CLICK PLUS Improper Resource Shutdown or Release",
  "vendor": "AutomationDirect",
  "product": "CLICK PLUS C0-0x CPU firmware",
  "cvss": {
    "score": 8.2,
    "source": "cna",
    "vector": "CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all available device sessions in the Remote PLC application.",
  "cwe": "CWE-404",
  "cvss_by_source": {
    "cna": 8.2
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "AutomationDirect",
        "product": "CLICK PLUS C0-0x CPU firmware",
        "ranges": [
          "\u003c v3.71"
        ],
        "fixed_in": [
          "v3.71"
        ]
      },
      {
        "vendor": "AutomationDirect",
        "product": "CLICK PLUS C0-1x CPU firmware",
        "ranges": [
          "\u003c v3.71"
        ],
        "fixed_in": [
          "v3.71"
        ]
      },
      {
        "vendor": "AutomationDirect",
        "product": "CLICK PLUS C2-x CPU firmware",
        "ranges": [
          "\u003c v3.71"
        ],
        "fixed_in": [
          "v3.71"
        ]
      }
    ],
    "solutions": [
      "AutomationDirect recommends that users update CLICK PLUS and firmware to  V3.80. https://www.automationdirect.com/support/software-downloads \n\nIf the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed:\n\n  *  Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure.\n  *  Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication.\n  *  Access Control – Restrict both physical and logical access to authorized personnel only.\n  *  Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.\n  *  Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.\n  *  Logging \u0026 Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity.\n  *  Backup \u0026 Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.\n  *  Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly."
    ],
    "upgrade": [
      "Upgrade CLICK PLUS C0-0x CPU firmware to v3.71 or later.",
      "Upgrade CLICK PLUS C0-1x CPU firmware to v3.71 or later.",
      "Upgrade CLICK PLUS C2-x CPU firmware to v3.71 or later."
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}