  "id": "CVE-2025-24482",
  "url": "https://poc.griffinguard.io/cve/CVE-2025-24482",
  "published_at": "2025-01-28T20:59:50.868Z",
  "title": "FactoryTalk® View Site Edition - Local Code Injection",
  "vendor": "Rockwell Automation",
  "product": "FactoryTalk® View Site Edition",
  "cvss": {
    "score": 7,
    "source": "cna",
    "vector": "CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:N"
  },
  "kev": {
    "in_kev": false,
    "added_at": null,
    "days_after_publication": null
  },
  "first_poc": null,
  "poc_repo_count": 0,
  "exploit_count": 0,
  "suspicious_repo_count": 0,
  "edge_device": null,
  "description": "A Local Code Injection Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect default permissions and allows for DLLs to be executed with higher level permissions.",
  "cwe": "CWE-94",
  "cvss_by_source": {
    "cna": 7
  },
  "repos": [],
  "remediation": {
    "affected": [
      {
        "vendor": "Rockwell Automation",
        "product": "FactoryTalk® View Site Edition",
        "ranges": [
          "\u003cV15"
        ],
        "fixed_in": null
      }
    ],
    "solutions": [
      "Upgrade to V15 or apply patch. Answer ID 1152304"
    ],
    "workarounds": [
      "Check the environment variables (PATH), and make sure FactoryTalk® View SE installation path (C:\\Program Files (x86)\\Common Files\\Rockwell) is before all others"
    ]
  },
  "exploit_refs": [],
  "hunt_profile": [],
  "rules": []
}